-
Protection Funtions
-
Overview
-
Protection Function
- When active
- Available Options:Warning/Trip/Off
- Automatic Fault Reset Possible
-
Electronic Overload
- Always
- Trip
- Yes
-
Electronic Overload Prewarning
- Always
- Warning
-
Locked Rotor
- During motor start
- Trip
-
High Current
- After motor start
- Separate warning and trip levels / off. Optional delay.
-
Low Current
- After motor start
- Separate warning and trip levels / off. Optional delay.
-
Imbalance
- Always ( Motor current > 60% of Ie and all therr phases available )
- Separate warning and trip levels / off. Optional delay.
- Yes
-
Phase Loss Protection
- Always ( Motor current > 60% of Ie )
- Trip, Off
-
PTC Protection
- Always
- Trip, Warning, Off
- Yes ( excluding PTC wire break and short circuit )
-
Earth Fault Protection
- Configurable
- Trip, Warning, Off
-
Load Shedding / Voltage DIP
- Always
- See subsection voltage DIP
-
Details
-
Electronic Overload Protection
-
Block Diagram
- relate parameter
- cooling time
- 1KW: 10min
- 5KW: 15min
- cooling mode
- trip class
- the trip classes 5 and 10 are allowed because the appropriate times (3s, 6s) are below the time Te of the motor (including the tolerance 10% of the UMC)
- Ia: the actual time
- Ie: the nominal current
- Te: the maximal heating time as defined by the motor manufacturer
- current Ie1 and optionally Ie2
- nominal current of motor for speed1 or speed2
- current factor
- restart level
- thermal load Pre-Warning level
- fault autoreset
-
Long Start, Locked Motor Protection
- Block Diagram
-
High Current Protection
- Block Diagram
-
Low Current Protection
- Block Diagram
-
Phase Loss Protection
- Block Diagram
-
Phase Imbalance Protection
- Block Diagram
-
Phase Sequence Protection
- Block Diagram
-
Motor Protection with Thermistor(PTC) acc. to EN 60947-8(type A sensors)
- Block Diagram
-
Earth Fault Protection with CEM11
- Block Diagram
-
Voltage Dips, Load Shedding
- Block Diagram
-
Management Functions
-
Starting and Stopping the Motor
- Digital Inputs
- DCS/PLC
- LCD-Panel
- Service Tool
-
Emergency Start
- Parameterise DI0,DI1 or DI2 as emergency start input
- From the control system / fieldbus
-
Checkback Monitoring
- For checkback via contactors one auxiliary contacts must be installed and wired to the UMC's DI0. Related Parameters: Checkback Time & Checkback Mode.
-
Transparent
- the outputs DO0...DO3 and the inputs DI0...DI5 are directly connected to the fieldbus and are independent of the overload status,if a fault output(DO2 or DO3) is activated by configuration the relevant output cannot be controlled from the fieldbus anymore but is controlled by the UMC itself.
-
Overload Relay
- Like Transparent, but is DO2...DO3. After powering up, contact DO0 immediately closes and contact DO1 open, fault behaviour, contact DO0 opens, contact DO1 closes.
-
Direct Starter(DOL)
- DI0:contactor checkback supervision
- DI4:start
- DI5:stop
- DO0:control function
-
Reversing Starter(REV)
- DI0:contactor checkback supervision
- DI3:start reverse
- DI4:star forward
- DI5:stop
- DO0:start the motor in a forward direction
- DO1:start the motor in a reverse direction
-
Star-Delta Starter
- DI0:contactor checkback supervision
- DI4:start
- DI5:stop
- DO0:control the star contactor
- DO1:control the delta contactor
- DO2:control the main contactor
-
Pole-Changing Starter
-
Two-Pole Motor
- DI0:contactor checkback supervision
- DI3:speed 2
- DI4:speed 1
- DI5:stop
- DO0:start the motor at speed 1
- DO1:start the motor at speed 2
- Dahlander Motor
-
Actuator 1-4
- DI0:limit open
- DI1:limit closed
- DI3:torque open/closed
- DI4:open
- DI5:close
- Fieldbus Communication
-
Inputs and Outputs
-
IO modules
-
DX111-FBP
- 8 DI(24V DC)
- 4 DO
- 1 AI
-
DX122-FBP
- 8 DI(110V AC - 230V AC)
- 4 DO
- 1 AI
-
Digital inputs
- Multifunction Inputs DI0-DI2
- Inputs DI3-DI5
- Relay outputs
- Metering, Monitoring and Diagnosis
-
Function Block Programming
- The custom application editor is integrated in the PBDTM